The browser you are using is not supported by this website. All versions of Internet Explorer are no longer supported, either by us or Microsoft (read more here: https://www.microsoft.com/en-us/microsoft-365/windows/end-of-ie-support).

Please use a modern browser to fully experience our website, such as the newest versions of Edge, Chrome, Firefox or Safari etc.

Modeling of room fire growth - Combustible lining materials

Author

  • Sven Erik Magnusson
  • Björn Sundström

Summary, in English

A computational procedure has been developed to correlate the room fire test process and results from the proposed IS0 small scale laboratory tests. The analysis assumes that the full scale room fire test follows the proposed ASTM method, implying that the lining material covers ceiling and walls. The procedure requires that the heat release measurement response time of the test room is evaluated and for a specific material linked to results from the ignitability test. From the same

test, a value of koc must be calculated. From a small scale rate of heat release test are evaluated specific characteristics describing the RHR-curve. The derived test room and material characteristics are used as input data to an uncomplicated mathematical expression, essentially describing the full scale test fire process as a concurrent flame spread phenomenon. Undetermined parametors in the model have boon derived using regression analysis and results from seven full scale room tests. In these the tested materials were of such thickness that no burning through occurred. The quantitative accuracy was thought acceptable but further experimental confirmation

and sensitivity studies are needed to assess the inherent variability. Qualitatively the procedure predicted the same relative ranking of materials as the room test. For thin surface finish materials on a non-combustible base it was possible to derive a radically simple expression to be used as indication of the risk of flashover. Again, the final usefulness can only be evaluated on the basis of further experimental evidence. In summary, it is thought that a first step has been taken in the efforts to use results from small scale tests to rationally predict full scale fire growth (for one specified scenario) and rank materials.

Publishing year

1984

Language

English

Publication/Series

LUTVDG/TVBB--3019--SE

Document type

Report

Publisher

Division of Building Fire Safety and Technology, Lund Institute of Technology

Topic

  • Building Technologies
  • Other Civil Engineering

Status

Published

Report number

3019