The browser you are using is not supported by this website. All versions of Internet Explorer are no longer supported, either by us or Microsoft (read more here: https://www.microsoft.com/en-us/microsoft-365/windows/end-of-ie-support).

Please use a modern browser to fully experience our website, such as the newest versions of Edge, Chrome, Firefox or Safari etc.

On-off Control of an Active Load for Power System Damping - Theory and Field Test

Author

Summary, in English

Controlled resistive loads can contribute to damping of electro-mechanical oscillations. This paper presents an on-off damping controller for a single machine system. It was used at a field test in Southern Sweden to damp oscillations of a 0.9 MW hydro power generator. The controller used estimated machine frequency as input and controlled a 20 kW resistive load via thyristor switches. The field measurements are compared to time simulations and a systematic procedure for tuning the controller is given. The results indicate that on-off control of active loads is effective in terms of added damping and that it is simple to tune and implement

Publishing year

1999

Language

English

Pages

608-613

Publication/Series

IEEE Transactions on Power Systems

Volume

14

Issue

2

Document type

Conference paper

Topic

  • Other Electrical Engineering, Electronic Engineering, Information Engineering

Keywords

  • control system analysis control system synthesis damping hydroelectric generators hydroelectric power on-off control oscillations power system control

Conference name

IEEE Power Engineering Society 1999 Winter Meeting

Conference date

1999-01-31

Conference place

Piscataway, New York, United States

Status

Published

ISBN/ISSN/Other

  • ISSN: 0885-8950