Wood Chip Refiner Control
Author
Summary, in English
The authors treat the control of a chip refiner to produce wood pulp, where the incremental gain between the motor load and the plate gap is subject to sudden changes due to pad collapse. Passive adaptive control with fault detection, active suboptimal dual control, and dual-control solutions are discussed. For dual control, the choice of the control criterion is crucial, as it must reflect the peculiarities of the process. Two nonquadratic performance indices are proposed, and the myopic solutions are computed. Simulations show the superior performance offered by these indices.<>
Department/s
Publishing year
1988
Language
English
Pages
38-43
Publication/Series
IEEE Control Systems Magazine
Volume
8
Issue
2
Document type
Journal article
Publisher
IEEE - Institute of Electrical and Electronics Engineers Inc.
Topic
- Control Engineering
Status
Published
ISBN/ISSN/Other
- ISSN: 0888-0611